Title: Evaluation on four sampling schemes for assessing indoor air quality
Authors: Wong, LT 
Mui, KW 
Keywords: Carbon dioxide (CO2)
Confidence level
Indoor air quality (IAQ)
Sampling period
Issue Date: 2007
Publisher: Pergamon Press
Source: Building and environment, 2007, v. 42, no. 3, p. 1119-1125 How to cite?
Journal: Building and environment 
Abstract: Continuous sampling is one of the common approaches for assessing indoor pollutant level. It is believed that the longer the measurement time, the higher the accuracy and confidence level of the measurement can be achieved. In 2003, the Hong Kong Environmental Protection Department (HKEPD) launched an Indoor Air Quality (IAQ) certification scheme to promote an acceptable IAQ in workplaces. However, measurement efforts and uncertainties associated with the sampling method have not been addressed. Alternative sampling schemes taking shorter measurements in the sampling period were proposed in some circumstances. In this study, the average carbon dioxide (CO2) concentration of a workplace is selected as an indicator of the indoor air quality to investigate the probable errors and measurement efforts in four sampling schemes, regarding the sampling period: in Scheme A, it is from a continuous sampling throughout the measurement; in Scheme B, it is from two sampling periods of two equal sessions of the measurement; in Scheme C, it is from two structural sampling periods of the two sessions; and in Scheme D, the average concentration is from four sampling periods in four equal sessions of the measurement. In particular, a year-round indoor CO2 concentration at 17 locations in a typical office in Hong Kong was used to evaluate the probable errors using these four sampling schemes. At certain confidence levels, the required measurement times of the alternative sampling schemes (Schemes B, C, D) were evaluated and compared with that of an 8-hour continuous one (Scheme A). It was found that Scheme C would offer a reduction of measurement effort up to 30%. It is recommended to specify the uncertainties and efforts of measurement in future codes, and to consider these sampling schemes in determining practical strategies for IAQ measurement.
URI: http://hdl.handle.net/10397/20025
ISSN: 0360-1323
EISSN: 1873-684X
DOI: 10.1016/j.buildenv.2005.11.014
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

13
Last Week
0
Last month
0
Citations as of Aug 13, 2017

WEB OF SCIENCETM
Citations

9
Last Week
0
Last month
0
Citations as of Aug 12, 2017

Page view(s)

33
Last Week
1
Last month
Checked on Aug 13, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.