Title: Electrical and thermal analysis of parallel single-Conductor cable installations
Authors: Du, YP 
Wang, XH
Keywords: Cables (electric)
Conductors (electric)
Electric properties
Thermal analysis
Issue Date: 2009
Publisher: IEEE
Source: IEEE Industry Applications Society Annual Meeting, 2009 : IAS 2009, 4-8 October 2009, Houston, TX, p. 1-6 How to cite?
Abstract: The unequal current distribution in parallel single-conductor cable installations can lead to an excessive temperature rise. This paper presented a cable model and a procedure of coupled electrical and thermal analysis for the evaluation of currents, losses and temperatures in the cables of concern. The cable model and analytic method were validated experimentally in the laboratory. The procedure was applied to evaluate the current rating, the temperature rise in a particular single-conductor installation. It is concluded that the parallel cable installation without proper cable rephrasing de-rates the cables significantly. The 3rd order harmonic current can cause a significant reduction of the current rating if its distortion is over 30%.
URI: http://hdl.handle.net/10397/17471
ISBN: 978-1-4244-3475-6
978-1-4244-3476-3 (E-ISBN)
ISSN: 0197-2618
DOI: 10.1109/IAS.2009.5324885