Abstract: A proposed alternative control strategy is implemented on site and compared with the original control strategy for variable speed pumps in a Hong Kong based 1,608 ft high-rise building with a floor area of 3.4 million ft 2. The results from the site tests and simulation study showed that significant chilled water pumps energy can be saved when using this alternative control strategy. Compared with the original control strategy, about 12.02% to 16.01% of the energy of the pumps distributing water to heat exchangers can be saved when the alternative control strategy is used. The annual energy saving of all variable speed primary pumps in the building by using the alternative control strategy is found to be about 251,869 kWh. Over several months, the site application of the alternative control strategy demonstrated that it can provide stable and reliable control in practical applications.
URI: http://hdl.handle.net/10397/15924
ISSN: 0001-2491
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

2
Last Week
0
Last month
Citations as of Nov 17, 2017

WEB OF SCIENCETM
Citations

4
Last Week
0
Last month
0
Citations as of Nov 18, 2017

Page view(s)

35
Last Week
4
Last month
Checked on Nov 20, 2017

Google ScholarTM

Check



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.