Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/15472
Title: Commissioning of AHU sensors using principal component analysis method
Authors: Xiao, F 
Wang, S 
Issue Date: 2003
Publisher: SAGE Publications
Source: Building services engineering research and technology, 2003, v. 24, no. 3, p. 179-189 How to cite?
Journal: Building services engineering research and technology 
Abstract: Principal component analysis (PCA) models are implemented for monitoring and fault detection and diagnosis (FDD) of air-handling units (AHUs), which is modified to solve the problems caused by the nonlinearity and variations in the environment. Independent heat balance and pressure-flow balance models are developed to reduce the effects of the system nonlinearity and to make the PCA method valid in different control modes. Sensor faults are detected and partly isolated using Q-statistic (square prediction error) and Q-contribution plot. Simulation tests are conducted to demonstrate the use of the PCA method for automatic commissioning of AMD monitoring instrumentations and to validate the PCA method in detecting and diagnosing the AHU sensor faults under various typical operating conditions.
URI: http://hdl.handle.net/10397/15472
ISSN: 0143-6244
EISSN: 1477-0849
DOI: 10.1191/0143624403bt070oa
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

2
Last Week
0
Last month
0
Citations as of Dec 7, 2017

Page view(s)

38
Last Week
1
Last month
Checked on Dec 10, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.