Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/15443
Title: Condensing temperature control to enhance the efficiency of air-cooled chillers
Authors: Yu, FW
Chan, KT 
Issue Date: 2004
Publisher: SAGE Publications
Source: Building services engineering research and technology, 2004, v. 25, no. 4, p. 279-294 How to cite?
Journal: Building services engineering research and technology 
Abstract: This paper describes an operating strategy of condensing temperature control (CTC), which means regulating the set point of condensing temperature based on the outdoor temperature, to enhance the efficiency of air-cooled chillers used in air-conditioned buildings. A mathematical model of an air-cooled chiller is developed for simulation and is validated by using the operating data of an existing chiller and of an experimental chiller. Compared to head pressure control (HPC) with a fixed set point of condensing temperature, CTC brings a moderate rise in the condensing temperature above the outdoor temperature, and hence enables the compressors to operate at a lower condensing pressure through staging more condenser fans. While more condenser fan power is consumed, compressor power can drop considerablely, reducing the annual chiller power consumption by 18.4%. It is suggested that the condensing temperature can be coupled with the outdoor temperature and the part load ratio of chillers to gauge the achievable part load efficiency.
URI: http://hdl.handle.net/10397/15443
ISSN: 0143-6244
EISSN: 1477-0849
DOI: 10.1191/0143624404bt095oa
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

12
Last Week
0
Last month
0
Citations as of Sep 19, 2017

Page view(s)

43
Last Week
1
Last month
Checked on Sep 17, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.