Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/14469
Title: A Method to generate effective cooling load factors for stratified air distribution systems using a floor-level air supply
Authors: Xu, H
Gao, N
Niu, J 
Issue Date: 2009
Publisher: Taylor & Francis
Source: HVAC and R research, 2009, v. 15, no. 5, p. 915-930 How to cite?
Journal: HVAC and R research 
Abstract: A vertical temperature gradient is known to occur in an enclosure that is ventilated by stratified air distribution (STRAD) methods. Thermal stratification offers distinct energy-saving possibilities. For example, a portion of heat gains can be excluded when calculating the air supply rate and the air-conditioning load. The cooling load reduction of a heat source depends primarily on its vertical location and radiant and convective split. In this study, an effective cooling load factor (ECLF) was defined to calculate the effective heat gains, which can be used by design engineers for the determination of the reduced-supply airflow rate and reduced cooling coil loads for common- and split-return/exhaust configurations with STRAD. Numerical simulations used to obtain these factors for various internal heat sources in a small office were presented, and on-site measurements were carried out to validate the performance of computational fluid dynamics in predicting the thermal stratification in large spaces. A fully developed database of ECLFs will be very useful when designing such systems.
URI: http://hdl.handle.net/10397/14469
ISSN: 1078-9669
EISSN: 1938-5587
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

7
Citations as of Feb 12, 2016

WEB OF SCIENCETM
Citations

7
Last Week
0
Last month
0
Citations as of Aug 22, 2017

Page view(s)

44
Last Week
0
Last month
Checked on Aug 20, 2017

Google ScholarTM

Check



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.