Title: Direct control algorithm for doubly fed induction generators in weak grids
Authors: Wong, KC
Ho, SL 
Cheng, KWE 
Issue Date: 2009
Source: IET Electric power applications, 2009, v. 3, no. 4, p. 371-380 How to cite?
Journal: IET Electric Power Applications 
Abstract: An algorithm utilising direct feedbacks of torque and reactive power for the control of a doubly fed induction generator (DFIG) is proposed. Although the algorithm is based on field-oriented control, the algorithm calculates the feedback and feed-forward variables in the stator reference frame to reduce the number of coordinate transformations. Since the algorithm uses a single-loop approach instead of a cascaded loop design, the tuning of the controller is easier and the response time is faster when compared to those of most existing methods. The internal model control (IMC) design method is used in the proposed scheme to formulate the controller parameters. Measures on the possible voltage variations are included to increase the robustness of the system. Computer simulation and experimental implementation are reported. The results show that the algorithm can control the torque and reactive power independently. Harmonic distortions generated by the system are not noticeable because of the use of constant switching frequency.
URI: http://hdl.handle.net/10397/14136
ISSN: 1751-8660
DOI: 10.1049/iet-epa.2008.0039
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

17
Last Week
0
Last month
0
Citations as of Sep 24, 2017

WEB OF SCIENCETM
Citations

11
Last Week
0
Last month
0
Citations as of Sep 23, 2017

Page view(s)

39
Last Week
0
Last month
Checked on Sep 24, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.