Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/12183
Title: Theoretical study of water mist system in building fire extinguishment
Authors: Li, YF
Li, JM
Chow, WK 
Sun, YY
Keywords: Cycling discharge
Fire extinguishment
Water mist
Zone model
Issue Date: 2006
Publisher: 北京工業大學學報編輯部
Source: 北京工業大學學報 (Journal of the Beijing Polytechnic University), 2006, v. 32, no. 9, p. 802-807 How to cite?
Journal: 北京工業大學學報 (Journal of the Beijing Polytechnic University) 
Abstract: A one-zone transient model is developed for obstructed fire where extinguishments primarily occur as a result of reduction in oxygen concentration due to consumption of oxygen by fire and dilution of oxygen with water vapor. The model is based on mass conservation of gas species and conservation of energy. This model is used to predict the fire extinguishments by water mist system under the continuous and cycling discharge modes. There is a good agreement between numerical and experimental results in air temperature and dry oxygen concentration. In addition, results show that cycling discharge water mist system would give more rapid extinguishment and consume less water for the obstructed fire in comparing with the continuous discharge mode.
URI: http://hdl.handle.net/10397/12183
ISSN: 0254-0037
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page view(s)

41
Last Week
1
Last month
Checked on Sep 18, 2017

Google ScholarTM

Check



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.