Title: Turbulent convection of air-cooled rectangular duct with surface-mounted cross-ribs
Authors: Wong, TT
Leung, CW 
Li, ZY
Tao, WQ
Keywords: Forced convection enhancement
Rectangular duct with cross-ribs
Turbulent heat transfer
Zonal k-ε model: SGSD and BIM
Issue Date: 2003
Publisher: Pergamon Press
Source: International journal of heat and mass transfer, 2003, v. 46, no. 24, p. 4629-4638 How to cite?
Journal: International journal of heat and mass transfer 
Abstract: Experimental and numerical studies were conducted to investigate the forced convection and flow friction of a turbulent airflow in a horizontal air-cooled rectangular duct, with square-sectioned cross-ribs mounted on its bottom surface. Cross-sectional dimensions of the cross-ribs were 6.37 mm × 6.37 mm. Reynolds number of the fully turbulent flow was maintained constant at 12,380. Heat was supplied uniformly to the airflow via bottom surface of the duct only. Effects of varying the angle formed by the cross-ribs between 30° and 120° on the forced convection and flow friction were studied. It was found that an optimum angle corresponding to the highest heat transfer coefficient occurred between 60° and 70°. Computational predictions of forced convection and flow friction of the same rectangular duct mounted with cross-ribs were performed with the zonal k-ε model, the stability-guaranteed second-order difference scheme and the block implicit method. A comparison with the experimental results indicated that a reasonably good agreement had been achieved. Existence of an optimum angle formed by the cross-ribs between 60° and 70° was also indicated, except the numerical predictions were lower than the experimental findings by approximately 2-10%. However, the flow friction had been slightly over-estimated by 2-11% with the numerical model. It was shown that forced convection could be enhanced sufficiently by mounting cross-ribs on the internal surfaces of a rectangular duct, especially when the optimum angle was used.
URI: http://hdl.handle.net/10397/10648
ISSN: 0017-9310
EISSN: 1879-2189
DOI: 10.1016/S0017-9310(03)00298-9
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

16
Last Week
0
Last month
0
Citations as of Sep 15, 2017

WEB OF SCIENCETM
Citations

16
Last Week
0
Last month
0
Citations as of Sep 22, 2017

Page view(s)

39
Last Week
1
Last month
Checked on Sep 18, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.