Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/10350
Title: Simulation on natural smoke filling in atrium with a balcony spill plume
Authors: Chow, WK 
Li, J
Issue Date: 2001
Source: Journal of fire sciences, 2001, v. 19, no. 4, p. 258-283 How to cite?
Journal: Journal of Fire Sciences 
Abstract: The smoke-filling process in atria of local shopping malls was studied. The scenario of smoke spreading from a shop located adjacent to an atrium was considered. A two-layer zone model, CL-Atrium, was developed with balcony spill plume. Three plume expressions due to Thomas et al., Poreh et al. and NFPA-92B were used and assessed. Comparison was made with simulations due to CFAST. It is found that a condition has to be satisfied for the plume expression due to Thomas et al. Further, the results on the smoke layer temperature and interface height in the atrium are similar while using the plume expressions by Poreh et al. and Thomas et al.
URI: http://hdl.handle.net/10397/10350
ISSN: 0734-9041
DOI: 10.1106/65LF-H4GA-9EW6-QF8E
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

10
Citations as of Feb 20, 2017

WEB OF SCIENCETM
Citations

9
Last Week
0
Last month
0
Citations as of Feb 22, 2017